SAGE.
Comparison Sheet

Sage vs
Generators.

Generators back the building. Sage backs egress. On many projects the answer is both, and taking the lighting layer off the genset lets it shrink, a downsize that often pays for Sage.

10 sec
NEC Activation
90 min
NFPA Runtime
No downtime
Genset Service
The Setup

Generators back the building.
Sage backs egress.

A generator is sized to carry the building's electrical load through utility outages: HVAC, refrigeration, computing, life-safety, the works. Emergency lighting is one fragment of that load schedule.

Code doesn't see it that way. NEC requires emergency lighting active within 10 seconds of utility failure. NFPA 101 requires 90 minutes of fail-safe operation. A generator's startup gap and single-point-of-failure exposure put both at risk unless a dedicated emergency-lighting layer is purpose-built into the system. That layer is what Sage is.

System Architecture

One power source. Two charging inputs.

Sage Central Battery accepts charging input from either the building's utility supply or a generator. Whether the generator is running or not, Sage keeps the batteries fully charged. The 24 VDC output feeds up to 8 emergency circuits in Class-2 MC daisy chain: fixtures, relay-converted luminaires, and exit signs all from the same source.

When utility power drops, Sage activates the EM layer instantly. The generator handles building load behind it.

SAGE CENTRAL BATTERY · SYSTEM ARCHITECTUREUTILITY SUPPLY120 VAC INPUT(277 / 480 V OPTION)GENERATOR SUPPLYCES INPUT(KEEPS CB CHARGED)SAGECENTRAL BATTERY100 / 250 /500 / 1000 W90 MIN @ 24 VDC24 VDCCKT 1CKT 2CKT 3CKT 4CKT 5CKT 6EXITEXITEXITCKT 7EXITEXITEXITCKT 8EXITEXITEXITUP TO (8) 24V EMERGENCY CIRCUITS100+ FIXTURES & EXITS PER CABINET · MC DAISY CHAINLEGENDSage CB / Relay FixtureExit Sign24V Class-2 MC
Sage Central Battery · dual-input · 24 VDC × 8 circuits
Better together

Take the lighting off the generator. It gets smaller.

A generator is sized for the whole building. Emergency lighting is a fragment of that load, but it drags a chain of dedicated infrastructure onto the genset: a utility-sensing transfer switch, dedicated feeders and EM panels, selective coordination, and a separate rated EPSS room.

Move the egress-lighting layer onto Sage and the generator no longer has to carry it or bring it up in ten seconds. Its life-safety scope shrinks, it can be specified smaller, and on many projects that downsize alone offsets the Sage system.

None of this is experimental. Low-voltage central battery is how Europe already lights egress, governed by its own standard, EN 50171, with 24–48 V systems from the industry's largest manufacturers. Sage brings the same architecture to the US, at a lower 24 VDC still.

Side by side

Three configurations. One code-bulletproof choice.

Generator aloneSage + GeneratorSage alone
NEC 10-second egress activation (NFPA 7.9.1.3)⚠ Up to 10 sec in darkness after utility loss✓ Sage activates instantly; generator picks up building load behind it✓ Sage activates instantly
Fail-safe behavior⚠ If generator fails during outage, EM fails✓ Generator maintains Sage battery charge in normal operation. If genset fails, Sage runs 90 min independently.✓ Sage runs 90 min independently — no moving parts
NFPA 7.9.2.3 single-branch failure⚠ Generator senses utility power, won't start on a downstream branch failure✓ Sage LCM (Olympus) activates EM immediately on single AC branch-circuit failure✓ Same — LCM-based
Repair / maintenance coverage (NEC 700.3(F))⚠ Code requires portable/temporary alternate source during repair✓ No downtime during generator service — Sage runs independently✓ No downtime — battery test cycle handles maintenance
Required ancillary equipment⚠ ALCR · BCET · Life-Safety ATS · Selective coordination · Dual-branch isolation · UL 924 devices✓ Sage layer removes the need for ALCR / BCET / UL 924 devices on EM circuits✓ None of those required
Wiring method⚠ Conduit + wire from generator to EM panels (~$9/ft material + install)✓ Sage uses Class-2 MC cable in a daisy chain (~$3/ft) — roughly 1/3 the conduit cost✓ Same — MC cable from cabinet to fixtures
Monthly + annual testing (NFPA 101)⚠ No feasible way to test the EM circuit on a generator — manual fixture-by-fixture testing required✓ Sage runs 30-sec monthly + 90-min annual tests automatically, logs results, emails faults✓ Same — automatic test cycle, compliance audit trail
Capital cost (mid-sized commercial)$$$$ Six-figure capital + fuel storage + ATS + emissions permit + separate EPSS room$ Sage adds a wall-mounted cabinet to an existing generator project$ Orders of magnitude lower than a generator alone
What Sage skips

Every acronym in the generator-only column above — ALCR, BCET, Life-Safety ATS, selective coordination, dual-branch isolation, UL 924 devices on EM circuits, a separate EPSS room, and a generator upsized for EM load — Sage removes them all.

The emergency-lighting branch collapses to a low-voltage Class 2 MC daisy chain, fed from one wall-mounted cabinet.

Where Sage fits

Two configurations. Two distinct conversations.

Project has a generator

Sage works alongside.

A generator carries the building. Sage carries the egress layer cleanly inside the same code framework. The generator keeps Sage's batteries fully charged in normal operation, and if the generator fails to start, Sage runs the emergency layer independently for 90 minutes.

This is the configuration most large commercial and institutional projects end up wanting once a code authority walks the spec.

No generator in the basis-of-design

Sage replaces the conversation.

Most schools, mid-rise commercial, multifamily, and many institutional facilities never had a generator in the basis-of-design. They were going to specify an emergency-lighting product regardless.

The choice isn't Sage or generator; it's Sage or integral battery packs. That comparison lives here →

For agencies

Hand this to a project with a generator in the spec.

Sage isn't the generator's competitor. It's the emergency-lighting layer that takes that generator from code-vulnerable to code-bulletproof, while removing a six-figure chunk of the BOM.