SAGE.
Engineer Tool · NEC Article 700Sage Beta

Load & Voltage-Drop Calculator

Per-circuit emergency-load aggregation + DC voltage-drop check, from conservative NEC-style guidance (5%) up to the 15% design limit Sage systems are engineered to at 24 VDC. Choose the wire-resistance basis, get wire-upsize recommendations when a circuit fails, and auto-size the Sage central battery.

Central battery bus
System Summary
144 W
Total load
6.0 A
Total current @ 24V
180 W
Sized (+25%)
Keystone
Recommended
⚠ 2 circuit(s) exceed the ceiling; see upsize recommendations below
Per-circuit analysis
CircuitWARunAWGVDVD %Pass
Circuit 1
10 × 8W
803.3315012 AWG
→ try 8 AWG
1.93V8.04% / 5%
Circuit 2
8 × 8W
642.6722012 AWG
→ try 8 AWG
2.26V9.44% / 5%
Engineering notes
  • 2 circuits exceed the 5% voltage-drop ceiling. Upsize recommendations shown per circuit.
  • Resistance values from NEC Chapter 9, Table 8 (copper, uncoated, DC, 75°C), the conservative hot-conductor basis. Sage systems are engineered to a 15% voltage-drop design limit at 24 VDC.
  • NEC 700.10(B): emergency-system wiring must be kept entirely independent of all other wiring. Route DC emergency runs in a separate raceway from normal-system AC circuits.
  • Fits a single Keystone 500W cabinet. Pair with Olympus local-circuit monitoring per lighting panel as needed.

Disclaimer:This calculator uses standard NEC-referenced resistance values and assumes uniform load across each circuit. Final branch sizing, OCPD selection, and raceway fill are the Engineer of Record's responsibility.